Buderus SB615
Specifications
Installation,
Operation, & Maintenance Manual
|
Model SB615 |
145 |
185 |
240 |
310 |
400 |
510 |
640 |
|
Performance Data |
|
|
|
|
|
|
|
|
Gas Input (MBH) |
506 |
644 |
845 |
1,080 |
1,393 |
1,776 |
2,228 |
|
Gross IBR Output (MBH)* |
484 |
612 |
791 |
1,022 |
1,317 |
1,678 |
2,104 |
|
Max Output Range (MBH)** |
440-484 |
560-612 |
730-791 |
940-1,022 |
1,220-1,317 |
1,550-1,678 |
1,950-2,104 |
|
Net IBR Raing (MBH) |
421 |
532 |
688 |
889 |
1,145 |
1,459 |
1,830 |
|
Thermal Efficiency (%) |
95.6 |
95 |
94.8 |
94.6 |
94.5 |
94.5 |
94.4 |
|
Combustion Efficiency (%) |
97.1 |
96.7 |
96.5 |
96.4 |
96.3 |
96.2 |
96.2 |
|
Boiler Horse Power |
14.4 |
18.2 |
23.6 |
30.5 |
39.3 |
50.1 |
62.8 |
|
Fireside Pressure Drop (in. wc) |
0.49 |
0.63 |
0.89 |
0.97 |
1.22 |
1.44 |
1.78 |
|
Piping Connections |
|
|
|
|
|
|
|
|
Vent Pipe Diameter |
7" |
7" |
8" |
8" |
10" |
12" |
12" |
|
Vent Connection Size |
11¾" |
11¾" |
12" |
12" |
13" |
14½" |
14½" |
|
Supply |
2½" |
2½" |
3" |
3" |
4" |
4" |
4" |
|
Return |
2½" |
2½" |
3" |
3" |
4" |
4" |
4" |
|
Physical Dimensions |
|
|
|
|
|
|
|
|
Overal Boiler Length (LG) |
68¾" |
68¾" |
70" |
70" |
70" |
75¼" |
75¼" |
|
Boiler Block Length (LK) |
60" |
60" |
61" |
61" |
61" |
66¼" |
66¼" |
|
Boiler Height |
54¼" |
54¼" |
55½" |
55½" |
63½" |
69¾" |
69¾" |
|
Boiler Width |
28¼" |
28¼" |
31¼" |
31¼" |
31¼" |
36¼" |
36¼" |
|
Dry Weight (lbs.) |
1,690 |
1,700 |
1,950 |
2,030 |
2,600 |
2,970 |
3,020 |
|
Water Content (gal) |
148 |
147 |
179 |
171 |
180 |
229 |
223 |
Buderus
SB735 Specifications
Installation,
Operation, & Maintenance Manual
|
Model
|
SB735/790 |
SB735/970 |
SB735/1200 |
|
Performance Data |
|
|
|
|
Gas Input (MBH) |
2,751 |
3,378 |
4,179 |
|
Gross IBR Output (MBH)* |
2,650 |
3,251 |
4,079 |
|
Max Output Range (MBH)** |
2,400-2,650 |
2,950-3,251 |
3,650-4,079 |
|
Net IBR Raing (MBH) |
2,265 |
2,827 |
3,547 |
|
Thermal Efficiency (%) |
96.9% |
96.3% |
97.6% |
|
Combustion Efficiency (%) |
94.7% |
95.6% |
96.5% |
|
Boiler Horse Power |
77.8% |
97% |
121.8% |
|
Fireside Pressure Drop (in. wc) |
1.98 |
2.31 |
2.6 |
|
Piping Connections |
|
|
|
|
Vent Pipe Diameter |
14" |
14" |
14" |
|
Vent Connection Size |
19" |
19" |
19" |
|
Supply |
4" |
5" |
5" |
|
Return |
4" |
5" |
5" |
|
Physical Dimensions |
|
|
|
|
Overal Boiler Length (LG) |
91½" |
108¼" |
108¼" |
|
Boiler Block Length (LK) |
75½" |
92" |
92" |
|
Boiler Height |
81¼" |
81¼" |
81¼" |
|
Boiler Width |
54 |
54 |
54 |
|
Dry Weight (lbs.) |
3,811 |
4,780 |
4,855 |
|
Water Content (gal) |
494 |
660 |
668 |
 |
Condensing Boiler
Technology
Condensing
boiler technology is them most efficient
form of gas heating available today.
Thanks to lower fuel consumption and
lower heating costs, condensing boilers
usually pay for themselves in only a few
years. An additional advantage: a
modern condensing heating system
increases the value of the building and
the quality of life by reducing
emissions.
Condensing Technology
Improves Energy Utilization by up to 15%
Condensing
technology utilizes a part of the energy
which normally disappears up the chimney
in other heating systems; the
condensation heat retained latently in
the flue gases. With condensing
technology, the water vapor contained in
the flue gases condense on the
relatively cool heat exchanger surfaces
of the boilers. The released heat
is transmitted directly into the boiler
water and thermal flue gas losses are
minimized. The seasonal efficiency
of the Buderus SB series condensing
boilers can reach up to 95%, reducing
heating costs by up to 20% in comparison
with conventional heating systems,
especially in radiant floor and snow
melt applications.
Lower Operating Costs
Compensate for Investment
Contemporary condensing boilers have a
higher initial purchase price than a
conventional boiler. However,
particularly in the medium and upper
capacity ranges, this extra initial
investment quickly pays for itself as
condensing technology saves so much
energy, resulting in substantially lower
heating costs.
Lower Boiler Return
Water Temperature Results in Higher
Efficiency
Condensation develops only if the return
flow temperature is below the dew point
of the combustion gases. Low flue
gas temperatures are achieved by means
of highly efficient heat exchanger
surfaces, two sated or full modulating
burners, and of course continuous
operation and low return water
temperatures. Condensing boilers
are ideally suited for direct piping in
commercial systems to make maximum use
of low return water temperatures which
lower system complexity, installation
costs, and maintenance costs.
High Energy
Utilization Through the Kondens® Heating
Surface
The
extremely efficient method of heat
generation using condensing technology
is further improved by the Buderus
Kondens®
heating surfaces. The secondary
heating surfaces are long and extremely
large in order to ensure optimal heat
transfer.
10% More Condensation
with Micro-Turbulence
A high
degree of condensation is achieved
through the intense contact of the
combustion gases with the heat transfer
surfaces. The Kondens®
heating surface, designed with a special
swirling effect, generates
micro-turbulence within each fire tube.
By channeling practically all combustion
gases to the cold heating surface, it
generated up to 10% more condensation
than a smooth heating surface. The
tapered design of the fire tubes also
helps to maintain a constant velocity of
the flue products with only a small loss
in pressure and increase heat transfer.
 |
Ultra High Efficiency
- Simple System Design
With
seasonal efficiencies up to 98%, the SB
Series of condensing boilers are among
the most efficient condensing boilers
available today. The Kondens
heating surface has been perfectly
designed to ensure efficient
condensation utilization. This
advanced technology is also conducive to
low NOx and CO levels, making this an
ideal choice for any application, but
especially for those needing to meet air
quality control regulations.
Innovative Boiler
Design: Higher Capacity in Less Space
The
Buderus SB Series Condensing Boilers are
an ideal solution for maximum energy
utilization. The full three-pass
boiler design with a full-pass
combustion chamber ensures compact
dimension and outstanding combustion
results. All components which ocme
into contact with combustion gases and
condensate are made of
corrosion-resistant 316 stainless steel,
which guarantees efficient heating
conditions for many years.
Simple System
Technology Reduces Planning Time and
Cost
The SB
Condensing Boilers have no operational
requirement with regard to water flow,
minimum return temperature, temperature
rise through the boiler, or minimum
burner capacity. Thus the heating
circuit flow and low temperature return
flow can be connected without any
additional equipment. In order to
achieve seasonal efficiencies of up to
98% optimal condensation is required -
separate return flow connection provides
the ideal practical solution. In
the Buderus SB boilers, the proportion
of low-temperature return water volume
of 20% of the total return flow is
adequate to achieve maximum efficiency.
|